Indiacation
|
PV (Character)
|
4 digits, 7 segments Green 10 mm height
|
|
SV (Setting Value)
|
4 digits, 7 segments Red 8 mm height
|
|
Various Function Indiacation
|
LED: Red (AL1, AL2, Out1, Out2 or RDY)
|
|
Control Method
|
PID Auto-Tuning PID Self- Tuning
|
Proportional bank (P1)
|
0.1 to 200.0% of setting limiter span
|
|
Proportional band (P2) at Output 2
|
0.10 to 10.00 times (Times per P)
|
|
Reset time (Integral) (I)
|
1 to 3600 sec (0: Off)
|
|
Rate time (Deviation) (D)
|
1 to 3600 sec (0: Off)
|
|
Cycle time (T1, T2)
|
1 to 120 sec
|
|
Dead band (D8)
|
-100.0 to +100.0 or -100 to +100C
|
|
On/Off
|
Control sensitivity (C1,C2)
|
0 to 999 or 0.0 to 999.9 C
|
|
Off Point of Output 1 & 2
|
Position of setting
|
-199 to 999 or 199.9 to 999.9 C
|
|
Control Output
|
Relay Contact
|
250V AC, 3A (Load resistance) 1 a contact (On heating/ cooling operation, output 2 is 250V AC, 2.4A load resistance, 1a contact
|
|
SSR Drive Voltage
|
0 to 12V DC (Load resistance: Max 600© or more)
|
|
Sampling Time
|
|
0.5 sec (Output change period is the same)
|
|
Setting and Indication Accuracy
|
Thermocouple
|
+-(0.3% + 1 digit) of process value or +-2C, either of bigger numerial values is taken. (Ambient temperature: 23C +- 10C) 100 to 0C: +- 3C, 200 to 100CL +- 4C Thermocouple B under 400C is not regulated
|
|
R.T.D.
|
+- (0.3% +- 1 digit) of process value or +- 0.9C, either of bigger numerical values is taken. (Ambient temperature: 23C +- 10C) Ambient temperature 23C +- (10C) Ambient temperature 0 to 50C: +- (0.5% +- digit) or 1.5C, either of bigger numerical values is taken
|
|
Memory Element
|
EEPROM
|
|
Voltage Source
|
100V AC to 240V AC (50/60Hz)
|
|
Weight
|
TTM-J4: less than 180g. TTM-J5: less than 240g
|
|
Power Consumption
|
Less than 10VA (240V AC)
|
|
Accessories
|
Instruction manual & installation attachment (TTM-J4) or installation meal instruments (TTM-J5)
|
|
Operating Condition
|
0 to 50C, 20 to 90%RH (under non- condensation)
|
|
Storage Condition
|
-25 to 70C, 5 to 95% RH (under non- condensation)
|
|
Functions
|
Manipurated Variable Limiter (ML1, MH1, ML2, MH2)
|
0.0 to 100.0%
|
|
Setting Limiter (SLL, SLH)
|
See Inpu and Range
|
|
Selectable Control Mode (CNT)
|
Auto-Tuning PID type A-B, Normal- Reverse, Auto- Tuning PID- On/Off
|
|
PV Correction Setting 0 point (PVS)
|
-199 to 999 or 199.9 to 999.9 ©
|
|
PV Correction Setting Gain
|
0.50 to 2.00 (times)
|
|
Input Filter
|
0 to 99 (sec)
|
|
Manual Reset (PBB)
|
0.0 to 100.0%, -100.0 to 100.0 (heating & cooling) of proportional band
|
|
Timer Operation Mode (TMM)
|
0.00 minute to 59.59 minutes, 0.00 hour to 99.59 hours: Accuracy: +- (1.5% +- 0.5sec) of setting time
|
|
Decimal Point Shift (DP)
|
Decimal point display available (up to 999.9)
|
|
Manual Control
|
Auto/Manual control can be switched by key
|
|
Run/Ready
|
Run and Ready can be switched by key
|
|
Blind Function
|
No indicaion available for non- required display
|
|
Auto-Tuning (AT) Coefficient
|
After AT, the computed PV band is newly to set up with another coefficient
|
|
FUNC key
|
Digit Shift Timer Start/Reset
|
|
Priority Display
|
Arbitrary parameter screens are shifted to indication of operation mode by key (max: 9 screens)
|
|
Lock Function (LOC)
|
4 modes (Off, All, Operation Lock, Lock except Operaion Mode)
|
|
Wach Dog Function
|
Data check by EEPROM (Err0), A/D converter check (Err1), and Auto-Tuning check (Err2), Built- in watch dog timer
|
|
Event Output 1 (AL1) Event Output 2 (AL2 or OUT2)
|
Function: PV contact output (8 modes), Special contact output (3 modes), additional functions (3 modes)
|
|
Setting Range: 199.9 to 999.9 or -1999 to 9999 C
|
|
Sensitivity: 0.0 to 999.9 or 0 to 9999 C
|
|
Rating: 250V AC 2.4A(Load resistance) 1a conact when selecting output 2at contact output 2, the output generates on cooling side during heaing/cooling. Contact polarity is selectable, either normal open or normal close
|
|
Heating & Cooling
|
See Control Output in standard specification
|